������������ ��                                                  APPLICATIONS

 

Energy managing & performance contracting

Sub metering for commercial tenants

Activity-based costing in commercial and industrial facilities

Real-time power monitoring

 

The world’s most cost-effective meter

 

Monitor energy parameters (kW, kWh, kVAR, PF, Amps, Volts) at up to 63 locations

     on a single RS-485 network...greatly reduces wiring time and cost

Fast split-core installation eliminates the need to remove conductors...saves time and labor

Precision metering electronics and current transformers in a single package–reduces

     the number of installed components– huge labor savings

Smart electronics eliminate CT orientation concerns–fast trouble-free installation

 

High accuracy

 

±1% total system accuracy, (10% to 100% of CT rating)

 

The Enercept H8035/8036 are innovative three-phase networked (Modbus RTU) power meters

that combine power metering electronics and high accuracy industrial grade CTs in a single package. The need for external electrical enclosures is eliminated, greatly reducing installation time and cost.

 

There are two application-specific platforms to choose from. The Basic Enercept Energy Meters (H8035) are ideal for sub metering applications where only kW and kWh are required. The Enercept Enhanced Data Stream meters (H8036) output 26 energy variables including

kW, kWh, volts, amps, and power factor, making them ideal for power monitoring and diagnostics.

Color-coordination between voltage leads and CTs makes phase matching easy. Additionally, these meters automatically detect and compensate for phase reversal, eliminating the concern of CT load orientation. Up to 63 power meters can be daisy chained on a single RS-485 network.

 

 

 

 

                                                 

                                      SPECIFICATIONS

 

Input Primary Voltage 208 to 480VAC RMS††

Number of Phases Monitored One to Three

Frequency 50/60Hz

Primary Current Up to 2400 amps cont. per phase††

Internal Isolation 2000VAC RMS

Insulation Class 600VAC RMS†††

Temperature Range 0° to 60°C (32° F to 140°F),50°C (122°F) for 2400A

Humidity Range 0 - 95% non-condensing

Systems Accuracy ±1% of reading from 10% to 100% of the rated current of the CTs...Accomplished by matching the CTs with a meter and calibrating them as a system

Output Physical Characteristics RS-485, 2 wire + shield

Baud Rate 9600, 8N1 format

Protocol Modbus RTU** (*)

 

** Detailed protocol specifications are available at: http:// www.veris.com/modbus/

* Other protocols available. Please consult factory.

†† Contact factory to interface for voltages above 480VAC or current above 2400 Amps

††† Do not apply 600V Class current transformers to circuits having a phase-to-phase voltage greater than 600V, unless adequate additional insulation is applied between the primary conductor and the current transformers. Veris assumes no responsibility for damage of equipment or personal injury caused by products operated on circuits above their published ratings.

  RTU** (*)

 

 

                                             

 

    H8035 Data Output Specifications

 

Data Output: kWh

     kW

 

    H8036 Data Output Specifications

 

Data output: kWh

                          Consumption kW

                          Real Power

                                                                           kVAR

                          Reactive power

   kVA

  Apparent power

  Power factor

  Average Real power

  Minimum Real power

  Maximum Real power

  Voltage, line to line

  Voltage, line to neutral†

  Amps

  Average current

               kW, Real power ØA†

   kW, Real power ØB†

   kW, Real power ØC†

 

INTEGRAL SUBMETERING SOLUTION ELIMINATES THE NEED FOR SEPARATE ENCLOSURES

 

Great for kW and kWh applications H8036 Outputs 26 energy variables including kW, kWh, volts, amps, and power factor † Based on derived neutral voltage


Enerceptâ Power Meter Model H8036 Series

Engineering Specifications

 

 

 

1.      The power meter shall consist of three split-core CTs hinged at both axis with the power metering electronics embedded inside of the master CT.  

 

2.      The meter shall measure true (rms) power, instantaneous demand (kW) and consumption (kWh).

 

3.      The meter shall report 26 energy variables serially over an RS-485 network using the Modbus (RTU) protocol, including kW: total, min/max/average, and per phase, kWh, kVAR, kVA, Power factor: total load and per phase, Voltage: line to line, line to neutral and for each phase, Amperage: average current and per phase.

 

4.      The consumption (kWh) variable shall be stored in non-volatile memory and retained in the event of a power outage.

 

5.      The meter shall directly accept any voltage input from 208-480 VAC.

 

6.      The meter shall be calibrated as a system and be accurate to +/- 1% from 10 % to 100 % of the rated current over a temperature range of 0-60° C.  

 

7.      The meter shall conform to ANSI C12.1 metering standards.

 

8.      The power meter shall be internally isolated to 2000 VAC.

 

9.      The power meter case isolation shall be 600 VAC.

 

10.  The power meter series shall have models available for amperage ranges of 100-2400 Amps.

 

11.  The Power Meter shall be Veris Industries model H8036

 

12.  The Power Meter meets UL508 safety standard for industrial control equipment